# Machine Power Page

> Per-machine 3-phase power analysis: live gauges, trends, accumulators, alert thresholds with templates, and alert history.

Each machine has a dedicated **Power** page at `/machines/:machineID/power`. It gives engineers a full electrical picture of a single machine, separate from the plant-wide [Main Electricity](https://docs.industrialpmr.com/dashboard/electricity-monitoring.md) view.

The page has four tabs.

| Tab | Purpose |
| :- | :- |
| **Real-Time Monitoring** | Live gauges and metric cards for the three phases and the total. |
| **Trend Analysis** | Hourly trend charts for voltage, current, power, and power factor. |
| **Data Grid** | All metrics in one table with min, max, and average per phase. |
| **Alert History** | Incidents raised by the per-machine alert thresholds. |

A status line at the top shows the connection state: **Connecting to device…**, **Restoring connection…**, **Device connected**, or **Device offline**.

> [!NOTE]
>
> Live streaming is started through a REST subscription that is renewed every **15 seconds** while the page is open.

***

## Real-Time Monitoring

![IndustrialPMR Real-Time Monitoring](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/Realtime-monitoring.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=165b1105d7c3ba1a67ff77e834854e41)

Phases R, S, and T are shown as **L1, L2, and L3**, plus the total (**SUM**). For each, the page shows:

* Voltage and current
* Active, apparent, and reactive power
* Power factor and frequency
* **Voltage THD** and **current THD** bars
* A **power-factor gauge**
* A **live frequency chart**

### THD Color Bands

![IndustrialPMR THD Color Bands](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/THD.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=33224d0c80839b49c0ad80f31178ada3)

| Measure | Green | Orange | Red |
| :- | :- | :- | :- |
| **Voltage THD** | under 5% | 5% to 8% | over 8% |
| **Current THD** | under 15% | 15% to 30% | over 30% |

## Trend Analysis

![IndustrialPMR Trend Analysis](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/Trend-analysis.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=5e75dd348fd987cdaa9ddd518e8f8d3e)

Hourly trend charts for **voltage**, **current**, **power**, and **power factor**.

## Data Grid

![IndustrialPMR Data Grid](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/data-grid.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=86decec4da121642ee408f592ef0a24b)

All metrics in a single table, with **min**, **max**, and **average** per phase and color-coded values.

***

## Accumulators

![IndustrialPMR Accumulators](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/Accumulators.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=4a5b8deacf3d8e392fef51e16cc6c676)

Accumulators are the energy counters kept for each machine:

* **Active energy**: import, export, total
* **Reactive energy**: inductive, capacitive, total
* **Apparent energy**

| Control | Description |
| :- | :- |
| **Reset schedule** | Set how often the counters reset (every *N* days, minimum 1) and the date of the last reset. |
| **Manual reset** | Zeroes all counters immediately and flags the request for the device. |

***

## Per-Machine Alert Thresholds

![IndustrialPMR Per-Machine Alert Thresholds](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/alert-threshold.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=025a8550a824834c1718ca0144ad80e5)

![IndustrialPMR Per-Machine Alert Thresholds](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/alert-current.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=5c82e147aeaa844b14431c16003a0606)

![IndustrialPMR Per-Machine Alert Thresholds](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/alert-pf.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=2d7f6b360b46401e0c71bef3e095983b)

Alerts can be configured for:

* Voltage L-N and Voltage L-L
* Current L1, L2, and L3
* Power Factor
* Voltage THD and Current THD

Each parameter has an **enabled** switch, an optional **minimum** and **maximum**, a **severity** (warning or critical), and a **hysteresis** percentage.

### Templates

Choose a template, then adjust any value:

| Template | Voltage L-N | Voltage L-L | PF minimum | Voltage THD max | Current THD max |
| :- | :- | :- | :- | :- | :- |
| **Conservative** | 220-240 V | 380-420 V | 0.90 | 3% | 10% |
| **Standard (IEEE/IEC)** | 207-253 V | 360-440 V | 0.85 | 5% | 15% |
| **Relaxed** | 195-265 V | 340-460 V | 0.80 | 8% | 30% |
| **Custom** | any values | | | | |

* Voltage and power-factor limits are **critical** severity.
* THD limits are **warning** severity.
* Current limits have **no default** and are set per machine capacity.

### Hysteresis

Hysteresis prevents alerts from flickering on and off. After a limit is breached, the value must recover past the limit by the hysteresis percentage before the alert clears.

| Parameter | Default hysteresis |
| :- | :- |
| Voltage | 2% |
| Power factor | 2% |
| Current | 3% |
| THD | 5% |

***

## Alert History

![IndustrialPMR Alert History](https://mintcdn.com/kunji-soft-technologies/Z3lxTECHchNjgmBJ/images/alert-analytics.png?fit=max\&auto=format\&n=Z3lxTECHchNjgmBJ\&q=85\&s=f0ad8362a5ff95908bf1088b9df02692)

The **Alert History** tab lists incidents with:

* Parameter and phase
* Limit, actual value, and peak value
* Severity
* Start, end, and duration

Filter by **All**, **Active**, or **Resolved**. Summary charts show the status split, severity mix, and recent incident trend.

> [!TIP]
>
> Currently active alerts also appear in a panel above the tabs, so they stay visible whichever tab you are on.